分类 | FNC NO. | 指令助记符 | 功能说明 | 对应不同型号的PLC | ||||
FX0S | FX0N | FX1S | FX1N |
FX2N FX2NC |
||||
程 序 流 程 |
00 | CJ | 条件跳转 | P | P | P | P | P |
01 | CALL | 子程序调用 | Î | Î | P | P | P | |
02 | SRET | 子程序返回 | Î | Î | P | P | P | |
03 | IRET | 中断返回 | P | P | P | P | P | |
04 | EI | 开中断 | P | P | P | P | P | |
05 | DI | 关中断 | P | P | P | P | P | |
06 | FEND | 主程序结束 | P | P | P | P | P | |
07 | WDT | 监视定时器刷新 | P | P | P | P | P | |
08 | FOR | 循环的起点与次数 | P | P | P | P | P | |
09 | NEXT | 循环的终点 | P | P | P | P | P | |
传 送 与 比 较 |
10 | CMP | 比较 | P | P | P | P | P |
11 | ZCP | 区间比较 | P | P | P | P | P | |
12 | MOV | 传送 | P | P | P | P | P | |
13 | SMOV | 位传送 | Î | Î | Î | Î | P | |
14 | CML | 取反传送 | Î | Î | Î | Î | P | |
15 | BMOV | 成批传送 | Î | P | P | P | P | |
16 | FMOV | 多点传送 | Î | Î | Î | Î | P | |
17 | XCH | 交换 | Î | Î | Î | Î | P | |
18 | BCD | 二进制转换成BCD码 | P | P | P | P | P | |
19 | BIN | BCD码转换成二进制 | P | P | P | P | P | |
算 术 与 逻 辑 运 算 |
20 | ADD | 二进制加法运算 | P | P | P | P | P |
21 | SUB | 二进制减法运算 | P | P | P | P | P | |
22 | MUL | 二进制乘法运算 | P | P | P | P | P | |
23 | DIV | 二进制除法运算 | P | P | P | P | P | |
24 | INC | 二进制加1运算 | P | P | P | P | P | |
25 | DEC | 二进制减1运算 | P | P | P | P | P | |
26 | WAND | 字逻辑与 | P | P | P | P | P | |
27 | WOR | 字逻辑或 | P | P | P | P | P | |
28 | WXOR | 字逻辑异或 | P | P | P | P | P | |
29 | NEG | 求二进制补码 | Î | Î | Î | Î | P | |
循 环 与 移 位 |
30 | ROR | 循环右移 | Î | Î | Î | Î | P |
31 | ROL | 循环左移 | Î | Î | Î | Î | P | |
32 | RCR | 带进位右移 | Î | Î | Î | Î | P | |
33 | RCL | 带进位左移 | Î | Î | Î | Î | P | |
34 | SFTR | 位右移 | P | P | P | P | P | |
35 | SFTL | 位左移 | P | P | P | P | P | |
36 | WSFR | 字右移 | Î | Î | Î | Î | P | |
37 | WSFL | 字左移 | Î | Î | Î | Î | P | |
38 | SFWR | FIFO(先入先出)写入 | Î | Î | P | P | P | |
39 | SFRD | FIFO(先入先出)读出 | Î | Î | P | P | P | |
数 据 处 理 |
40 | ZRST | 区间复位 | P | P | P | P | P |
41 | DECO | 解码 | P | P | P | P | P | |
42 | ENCO | 编码 | P | P | P | P | P | |
43 | SUM | 统计ON位数 | Î | Î | Î | Î | P | |
44 | BON | 查询位某状态 | Î | Î | Î | Î | P | |
45 | MEAN | 求平均值 | Î | Î | Î | Î | P | |
46 | ANS | 报警器置位 | Î | Î | Î | Î | P | |
47 | ANR | 报警器复位 | Î | Î | Î | Î | P | |
48 | SQR | 求平方根 | Î | Î | Î | Î | P | |
49 | FLT | 整数与浮点数转换 | Î | Î | Î | Î | P | |
高 速 处 理 |
50 | REF | 输入输出刷新 | P | P | P | P | P |
51 | REFF | 输入滤波时间调整 | Î | Î | Î | Î | P | |
52 | MTR | 矩阵输入 | Î | Î | P | P | P | |
53 | HSCS | 比较置位(高速计数用) | Î | P | P | P | P | |
54 | HSCR | 比较复位(高速计数用) | Î | P | P | P | P | |
55 | HSZ | 区间比较(高速计数用) | Î | Î | Î | Î | P | |
56 | SPD | 脉冲密度 | Î | Î | P | P | P | |
57 | PLSY | 指定频率脉冲输出 | P | P | P | P | P | |
58 | PWM | 脉宽调制输出 | P | P | P | P | P | |
59 | PLSR | 带加减速脉冲输出 | Î | Î | P | P | P | |
方 便 指 令 |
60 | IST | 状态初始化 | P | P | P | P | P |
61 | SER | 数据查找 | Î | Î | Î | Î | P | |
62 | ABSD | 凸轮控制(绝对式) | Î | Î | P | P | P | |
63 | INCD | 凸轮控制(增量式) | Î | Î | P | P | P | |
64 | TTMR | 示教定时器 | Î | Î | Î | Î | P | |
65 | STMR | 特殊定时器 | Î | Î | Î | Î | P | |
66 | ALT | 交替输出 | P | P | P | P | P | |
67 | RAMP | 斜波信号 | P | P | P | P | P | |
68 | ROTC | 旋转工作台控制 | Î | Î | Î | Î | P | |
69 | SORT | 列表数据排序 | Î | Î | Î | Î | P | |
外 部 I/O 设 备
|
70 | TKY | 10键输入 | Î | Î | Î | Î | P |
71 | HKY | 16键输入 | Î | Î | Î | Î | P | |
72 | DSW | BCD数字开关输入 | Î | Î | P | P | P | |
73 | SEGD | 七段码译码 | Î | Î | Î | Î | P | |
74 | SEGL | 七段码分时显示 | Î | Î | P | P | P | |
75 | ARWS | 方向开关 | Î | Î | Î | Î | P | |
76 | ASC | ASCI码转换 | Î | Î | Î | Î | P | |
77 | PR | ASCI码打印输出 | Î | Î | Î | Î | P | |
78 | FROM | BFM读出 | Î | P | Î | P | P | |
79 | TO | BFM写入 | Î | P | Î | P | P | |
外 围 设 备
|
80 | RS | 串行数据传送 | Î | P | P | P | P |
81 | PRUN | 八进制位传送(#) | Î | Î | P | P | P | |
82 | ASCI | 16进制数转换成ASCI码 | Î | P | P | P | P | |
83 | HEX | ASCI码转换成16进制数 | Î | P | P | P | P | |
84 | CCD | 校验 | Î | P | P | P | P | |
85 | VRRD | 电位器变量输入 | Î | Î | P | P | P | |
86 | VRSC | 电位器变量区间 | Î | Î | P | P | P | |
87 | – | – | ||||||
88 | PID | PID运算 | Î | Î | P | P | P | |
89 | – | – | ||||||
浮 点 数 运 算 |
110 | ECMP | 二进制浮点数比较 | Î | Î | Î | Î | P |
111 | EZCP | 二进制浮点数区间比较 | Î | Î | Î | Î | P | |
118 | EBCD | 二进制浮点数→十进制浮点数 | Î | Î | Î | Î | P | |
119 | EBIN | 十进制浮点数→二进制浮点数 | Î | Î | Î | Î | P | |
120 | EADD | 二进制浮点数加法 | Î | Î | Î | Î | P | |
121 | EUSB | 二进制浮点数减法 | Î | Î | Î | Î | P | |
122 | EMUL | 二进制浮点数乘法 | Î | Î | Î | Î | P | |
123 | EDIV | 二进制浮点数除法 | Î | Î | Î | Î | P | |
127 | ESQR | 二进制浮点数开平方 | Î | Î | Î | Î | P | |
129 | INT | 二进制浮点数→二进制整数 | Î | Î | Î | Î | P | |
130 | SIN | 二进制浮点数Sin运算 | Î | Î | Î | Î | P | |
131 | COS | 二进制浮点数Cos运算 | Î | Î | Î | Î | P | |
132 | TAN | 二进制浮点数Tan运算 | Î | Î | Î | Î | P | |
147 | SWAP | 高低字节交换 | Î | Î | Î | Î | P | |
定 位 |
155 | ABS | ABS当前值读取 | Î | Î | P | P | Î |
156 | ZRN | 原点回归 | Î | Î | P | P | Î | |
157 | PLSY | 可变速的脉冲输出 | Î | Î | P | P | Î | |
158 | DRVI | 相对位置控制 | Î | Î | P | P | Î | |
159 | DRVA | 绝对位置控制 | Î | Î | P | P | Î | |
时 钟 运 算 |
160 | TCMP | 时钟数据比较 | Î | Î | P | P | P |
161 | TZCP | 时钟数据区间比较 | Î | Î | P | P | P | |
162 | TADD | 时钟数据加法 | Î | Î | P | P | P | |
163 | TSUB | 时钟数据减法 | Î | Î | P | P | P | |
166 | TRD | 时钟数据读出 | Î | Î | P | P | P | |
167 | TWR | 时钟数据写入 | Î | Î | P | P | P | |
169 | HOUR | 计时仪 | Î | Î | P | P | ||
外 围 设 备 |
170 | GRY | 二进制数→格雷码 | Î | Î | Î | Î | P |
171 | GBIN | 格雷码→二进制数 | Î | Î | Î | Î | P | |
176 | RD3A | 模拟量模块(FX0N-3A)读出 | Î | P | Î | P | Î | |
177 | WR3A | 模拟量模块(FX0N-3A)写入 | Î | P | Î | P | Î | |
触 点 比 较 |
224 | LD= | (S1)= (S2)时起始触点接通 | Î | Î | P | P | P |
225 | LD> | (S1)> (S2)时起始触点接通 | Î | Î | P | P | P | |
226 | LD< | (S1)< (S2)时起始触点接通 | Î | Î | P | P | P | |
228 | LD<> | (S1)<> (S2)时起始触点接通 | Î | Î | P | P | P | |
229 | LD≦ | (S1)≦ (S2)时起始触点接通 | Î | Î | P | P | P | |
230 | LD≧ | (S1)≧ (S2)时起始触点接通 | Î | Î | P | P | P | |
232 | AND= | (S1)= (S2)时串联触点接通 | Î | Î | P | P | P | |
233 | AND> | (S1)> (S2)时串联触点接通 | Î | Î | P | P | P | |
234 | AND< | (S1)< (S2)时串联触点接通 | Î | Î | P | P | P | |
236 | AND<> | (S1)<> (S2)时串联触点接通 | Î | Î | P | P | P | |
237 | AND≦ | (S1)≦ (S2)时串联触点接通 | Î | Î | P | P | P | |
238 | AND≧ | (S1)≧ (S2)时串联触点接通 | Î | Î | P | P | P | |
240 | OR= | (S1)= (S2)时并联触点接通 | Î | Î | P | P | P | |
241 | OR> | (S1)> (S2)时并联触点接通 | Î | Î | P | P | P | |
242 | OR< | (S1)< (S2)时并联触点接通 | Î | Î | P | P | P | |
244 | OR<> | (S1)<> (S2)时并联触点接通 | Î | Î | P | P | P | |
245 | OR≦ | (S1)≦ (S2)时并联触点接通 | Î | Î | P | P | P | |
246 | OR≧ | (S1)≧ (S2)时并联触点接通 | Î | Î | P | P | P |
[ad]
取指令与输出指令(LD/LDI/LDP/LDF/OUT)
(1)LD(取指令) 一个常开触点与左母线连接的指令,每一个以常开触点开始的逻辑行都用此指令。
(2)LDI(取反指令) 一个常闭触点与左母线连接指令,每一个以常闭触点开始的逻辑行都用此指令。
(3)LDP(取上升沿指令) 与左母线连接的常开触点的上升沿检测指令,仅在指定位元件的上升沿(由OFF→ON)时接通一个扫描周期。
(4)LDF(取下降沿指令) 与左母线连接的常闭触点的下降沿检测指令。
(5)OUT(输出指令) 对线圈进行驱动的指令,也称为输出指令。
取指令与输出指令的使用说明:
1)LD、LDI指令既可用于输入左母线相连的触点,也可与ANB、ORB指令配合实现块逻辑运算;
2)LDP、LDF指令仅在对应元件有效时维持一个扫描周期的接通。
3)LD、LDI、LDP、LDF指令的目标元件为X 、Y 、M 、T、C、S;
4)OUT指令可以连续使用若干次(相当于线圈并联),对于定时器和计数器,在OUT指令之后应设置常数K或数据寄存器。
5)OUT指令目标元件为Y、M、T、C和S,但不能用于X。触点串联指令(AND/ANI/ANDP/ANDF)a、AND(与指令) 一个常开触点串联连接指令,完成逻辑“与”运算。b、ANI(与反指令) 一个常闭触点串联连接指令,完成逻辑“与非”运算。c、ANDP 上升沿检测串联连接指令。d、ANDF 下降沿检测串联连接指令。
触点串联指令的使用的使用说明:
1)AND、ANI、ANDP、ANDF都指是单个触点串联连接的指令,串联次数没有限制,可反复使用。
2)AND、ANI、ANDP、ANDF的目标元元件为X、Y、M、T、C和S。
3)OUT M101指令之后通过T1的触点去驱动Y4称为连续输出。触点并联指令(OR/ORI/ORP/ORF)
(1)OR(或指令) 用于单个常开触点的并联,实现逻辑“或”运算。
(2)ORI(或非指令) 用于单个常闭触点的并联,实现逻辑“或非”运算。(3)ORP 上升沿检测并联连接指令。(4)ORF 下降沿检测并联连接指令。
触点并联指令的使用说明:
1)OR、ORI、ORP、ORF指令都是指单个触点的并联,并联触点的左端接到LD、LDI、LDP或LPF处,右端与前一条指令对应触点的右端相连。触点并联指令连续使用的次数不限;
2)OR、ORI、ORP、ORF指令的目标元件为X、Y、M、T、C、S。
块操作指令(ORB / ANB)
(1)ORB(块或指令) 用于两个或两个以上的触点串联连接的电路之间的并联。
ORB指令的使用说明:
1)几个串联电路块并联连接时,每个串联电路块开始时应该用LD或LDI指令;
2)有多个电路块并联回路,如对每个电路块使用ORB指令,则并联的电路块数量没有限制;
3)ORB指令也可以连续使用,但这种程序写法不推荐使用,LD或LDI指令的使用次数不得超过8次,也就是ORB只能连续使用8次以下。
(2)ANB(块与指令) 用于两个或两个以上触点并联连接的电路之间的串联。
ANB指令的使用说明:
1)并联电路块串联连接时,并联电路块的开始均用LD或LDI指令;
2)多个并联回路块连接按顺序和前面的回路串联时,ANB指令的使用次数没有限制。也可连续使用ANB,但与ORB一样,使用次数在8次以下。
置位与复位指令(SET/RST)
(1)SET(置位指令) 它的作用是使被操作的目标元件置位并保持。
(2)RST(复位指令) 使被操作的目标元件复位并保持清零状态。SET、RST指令的使用,当X0常开接通时,Y0变为ON状态并一直保持该状态,即使X0断开Y0的ON状态仍维持不变;只有当X1的常开闭合时,Y0才变为OFF状态并保持,即使X1常开断开,Y0也仍为OFF状态。
SET 、RST指令的使用说明:
1)SET指令的目标元件为Y、M、S,RST指令的目标元件为Y、M、S、T、C、D、V 、Z。RST指令常被用来对D、Z、V的内容清零,还用来复位积算定时器和计数器。
2)对于同一目标元件,SET、RST可多次使用,顺序也可随意,但最后执行者有效。微分指令(PLS/PLF)(1)PLS(上升沿微分指令) 在输入信号上升沿产生一个扫描周期的脉冲输出。
(2)PLF(下降沿微分指令) 在输入信号下降沿产生一个扫描周期的脉冲输出。利用微分指令检测到信号的边沿,通过置位和复位命令控制Y0的状态。
PLS、PLF指令的使用说明:
1)PLS、PLF指令的目标元件为Y和M;
2)使用PLS时,仅在驱动输入为ON后的一个扫描周期内目标元件ON,M0仅在X0的常开触点由断到通时的一个扫描周期内为ON;使用PLF指令时只是利用输入信号的下降沿驱动,其它与PLS相同。
主控指令(MC/MCR)
(1)MC(主控指令) 用于公共串联触点的连接。执行MC后,左母线移到MC触点的后面。
(2)MCR(主控复位指令) 它是MC指令的复位指令,即利用MCR指令恢复原左母线的位置。在编程时常会出现这样的情况,多个线圈同时受一个或一组触点控制,如果在每个线圈的控制电路中都串入同样的触点,将占用很多存储单元,使用主控指令就可以解决这一问题。
MC、MCR指令,利用MC N0 M100实现左母线右移,使Y0、Y1都在X0的控制之下,其中N0表示嵌套等级,在无嵌套结构中N0的使用次数无限制;利用MCR N0恢复到原左母线状态。如果X0断开则会跳过MC、MCR之间的指令向下执行。
MC、MCR指令的使用说明:
1)MC、MCR指令的目标元件为Y和M,但不能用特殊辅助继电器。MC占3个程序步,MCR占2个程序步;
2)主控触点在梯形图中与一般触点垂直。主控触点是与左母线相连的常开触点,是控制一组电路的总开关。与主控触点相连的触点必须用LD或LDI指令。
3)MC指令的输入触点断开时,在MC和MCR之内的积算定时器、计数器、用复位/置位指令驱动的元件保持其之前的状态不变。非积算定时器和计数器,用OUT指令驱动的元件将复位,22中当X0断开,Y0和Y1即变为OFF。
4)在一个MC指令区内若再使用MC指令称为嵌套。嵌套级数最多为8级,编号按N0→N1→N2→N3→N4→N5→N6→N7顺序增大,每级的返回用对应的MCR指令,从编号大的嵌套级开始复位。
堆栈指令(MPS/MRD/MPP)堆栈指令是FX系列中新增的基本指令,用于多重输出电路,为编程带来便利。在FX系列PLC中有11个存储单元,它们专门用来存储程序运算的中间结果,被称为栈存储器。
a、MPS(进栈指令) 将运算结果送入栈存储器的第一段,同时将先前送入的数据依次移到栈的下一段。
b、MRD(读栈指令) 将栈存储器的第一段数据(最后进栈的数据)读出且该数据继续保存在栈存储器的第一段,栈内的数据不发生移动。
c、MPP(出栈指令) 将栈存储器的第一段数据(最后进栈的数据)读出且该数据从栈中消失,同时将栈中其它数据依次上移。
堆栈指令的使用说明:
1)堆栈指令没有目标元件;
2)MPS和MPP必须配对使用;
3)由于栈存储单元只有11个,所以栈的层次最多11层。
逻辑反、空操作与结束指令(INV/NOP/END)
a、INV(反指令) 执行该指令后将原来的运算结果取反。反指令的使用,如果X0断开,则Y0为ON,否则Y0为OFF。使用时应注意INV不能象指令表的LD、LDI、LDP、LDF那样与母线连接,也不能象指令表中的OR、ORI、ORP、ORF指令那样单独使用。
b、NOP(空操作指令) 不执行操作,但占一个程序步。执行NOP时并不做任何事,有时可用NOP指令短接某些触点或用NOP指令将不要的指令覆盖。当PLC执行了清除用户存储器操作后,用户存储器的内容全部变为空操作指令。
c、END(结束指令) 表示程序结束。若程序的最后不写END指令,则PLC不管实际用户程序多长,都从用户程序存储器的第一步执行到最后一步;若有END指令,当扫描到END时,则结束执行程序,这样可以缩短扫描周期。
在程序调试时,可在程序中插入若干END指令,将程序划分若干段,在确定前面程序段无误后,依次删除END指令,直至调试结束。
FX系列PLC的步进指令
1.步进指令(STL/RET)步进指令是专为顺序控制而设计的指令。在工业控制领域许多的控制过程都可用顺序控制的方式来实现,使用步进指令实现顺序控制既方便实现又便于阅读修改。FX2N中有两条步进指令:STL(步进触点指令)和RET(步进返回指令)。STL和RET指令只有与状态器S配合才能具有步进功能。如STL S200表示状态常开触点,称为STL触点,它在梯形图中的符号为-|| ||- ,它没有常闭触点。我们用每个状态器S记录一个工步,例STL S200有效(为ON),则进入S200表示的一步(类似于本步的总开关),开始执行本阶段该做的工作,并判断进入下一步的条件是否满足。一旦结束本步信号为ON,则关断S200进入下一步,如S201步。RET指令是用来复位STL指令的。执行RET后将重回母线,退出步进状态。
2.状态转移图一个顺序控制过程可分为若干个阶段,也称为步或状态,每个状态都有不同的动作。当相邻两状态之间的转换条件得到满足时,就将实现转换,即由上一个状态转换到下一个状态执行。我们常用状态转移图(功能表图)描述这种顺序控制过程。用状态器S记录每个状态,X为转换条件。如当X1为ON时,则系统由S20状态转为S21状态。状态转移图中的每一步包含三个内容:本步驱动的内容,转移条件及指令的转换目标。步驱动Y0,当X1有效为ON时,则系统由S20状态转为S21状态,X1即为转换条件,转换的目标为S21步。
3.步进指令的使用说明
1)STL触点是与左侧母线相连的常开触点,某STL触点接通,则对应的状态为活动步;
2)与STL触点相连的触点应用LD或LDI指令,只有执行完RET后才返回左侧母线;
3)STL触点可直接驱动或通过别的触点驱动Y、M、S、T等元件的线圈;
4)由于PLC只执行活动步对应的电路块,所以使用STL指令时允许双线圈输出(顺控程序在不同的步可多次驱动同一线圈);
5) STL触点驱动的电路块中不能使用MC和MCR指令,但可以用CJ指令;
6)在中断程序和子程序内,不能使用STL指令。